Return trip following service - 30/03/2026

Summary

Logged Date
2026-03-31
Owner
Sophie
Party
Sutton Farm Barns
Area
-
Priority
Standard
Resolved Date
2026-05-05
Signed Off By
-

Problem

System is tripping out main RCD and has gone into high level. Service completed 30/03/2026. Return trip scheduled for 31/03/2026.

Investigation And Action

Corrective Action

Replaced pump on customer approval.

Customer Feedback

-

Root Cause

Intermittent pump/floating-arm failure, likely pump degradation/age.

Preventative Action

Implement equipment age/usage tracking to anticipate component replacement and reduce avoidable return visits.

Review Effectiveness

Pump replaced; action for system/Luke to investigate incorporating equipment age into job records.

Status Update

Use this panel for all status changes. Main edit form does not change status.

Status History
FromToChanged AtByNote
InitialResolved2026-05-05 21:11:19management reviewTranscript summary: Return trip after service at Sutton Farm Barns: primary pump had intermittent float/operation issue; engineer adjusted float but failure recurred next day and pump was replaced at customer's request. Replacement pump fitted after intermittent failure; age-tracking action logged. Root cause check: partial - Technical fault correctly identified and remedied; broader preventative measure (age tracking) requires system work.