Alton Road STW
Control Panel for CRX14 not operating correctly on the backwash cycle, backwash blower failing to run. All backwash blowers were 0.8A or more on the information we had, so LME were setting the backwash current monitors to be healthy as long as it is over 0.7A. Due to the new blowers information stating the 120 blower is now 0.5A, it meant that this previous threshold was too high. And because this was the first CRX14, it is the first time we have encountered this particular issue. Solution will be LME to set current monitors at 0.4A
-
-
-
-
-
Use this panel for all status changes. Main edit form does not change status.
| From | To | Changed At | By | Note |
|---|---|---|---|---|
| - | Initial | 2026-05-14 07:47:57 | anonymous | - |